For demanding power distribution networks
The N2XS(FL)2Y meets the standards DIN VDE 0276-620, HD 620 S2 and IEC 60502. It is ideally suited for installation indoors, in cable ducts, outdoors, in soil, in water, and on cable trays – especially in utility grids, industrial plants, and switching stations, where high demands on mechanical strength and water resistance apply.
Technical construction
The cable design is based on a multi-stranded copper conductor (Class 2), an XLPE insulation with an extruded, tightly bonded outer conductive layer, and a longitudinally watertight, conductive tape. The shielding consists of copper wires with counter helix, complemented by an additional longitudinally watertight tape. The outer protection is achieved with a black PE sheath laminated with an aluminum tape – serving as an effective water barrier.
Properties and benefits
The N2XS(FL)2Y is suitable for underground installation, designed for outdoor use, and withstands operating temperatures up to +90 °C and short-circuit loads up to +250 °C. It is free from silicone and cadmium and contains no substances that interfere with paint wetting. Thanks to its partial discharge-free design and the Al/PE layer, it is ideally suited for humid environments with high safety requirements.