N2XS(FL)2Y

The N2XS(FL)2Y cable is a longitudinally watertight medium-voltage cable with a copper conductor, XLPE insulation, and a tightly bonded Al/PE sheath. It offers maximum operational safety for critical infrastructures and provides reliable protection against penetrating moisture.

N2XS(FL)2Y
For demanding power distribution networks
The N2XS(FL)2Y meets the standards DIN VDE 0276-620, HD 620 S2 and IEC 60502. It is ideally suited for installation indoors, in cable ducts, outdoors, in soil, in water, and on cable trays – especially in utility grids, industrial plants, and switching stations, where high demands on mechanical strength and water resistance apply.
Technical construction
The cable design is based on a multi-stranded copper conductor (Class 2), an XLPE insulation with an extruded, tightly bonded outer conductive layer, and a longitudinally watertight, conductive tape. The shielding consists of copper wires with counter helix, complemented by an additional longitudinally watertight tape. The outer protection is achieved with a black PE sheath laminated with an aluminum tape – serving as an effective water barrier.
Properties and benefits
The N2XS(FL)2Y is suitable for underground installation, designed for outdoor use, and withstands operating temperatures up to +90 °C and short-circuit loads up to +250 °C. It is free from silicone and cadmium and contains no substances that interfere with paint wetting. Thanks to its partial discharge-free design and the Al/PE layer, it is ideally suited for humid environments with high safety requirements.
The N2XS(FL)2Y meets the standards DIN VDE 0276-620, HD 620 S2 and IEC 60502. It is ideally suited for installation indoors, in cable ducts, outdoors, in soil, in water, and on cable trays – especially in utility grids, industrial plants, and switching stations, where high demands on mechanical strength and water resistance apply.

Technical Specifications

General Data

CPR class
Fca
Flame retardant
no
Maximal operating conductor temperature (°C)
+90 °C
Maximal short-circuit temperature (°C)
+250 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-20 °C
Shape of conductor
RM

6/10 kV

Voltage
6/10 kV
Test voltage
21 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
+90 °C
Short-circuit temperature (max.)
+250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeCap [uF/km]DI [mm]RI [Ohm/km]Wi [mm]Ibl [A]Ibe [A]Ik [kA]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x50/16CuRM0.2416.30.3873.42382207.12.1520261010
1x70/16CuRM0.2817.90.2683.4294268102.1560281238
1x95/16CuRM0.319.40.1933.435832013.62.1580291495
1x120/16CuRM0.3420.90.1533.441336317.12.1620311773
1x150/25CuRM0.3622.30.1243.446840521.42.1640322119
1x185/25CuRM0.423.90.0993.453545626.42.1680342483
1x240/25CuRM0.4426.40.0753.463152634.32.1720363073
1x300/25CuRM0.4828.80.063.472259142.92.1780393737
1x400/35CuRM0.5431.40.0473.482766257.22.1840424697
1x500/35CuRM0.6134.60.0373.494974471.42.1880445729

12/20 kV

Voltage
12/20 kV
Test voltage
42 kV
Operating temperature range
-35 - + 90 / -35 - +90 °C
Conductor temperature (max.)
+90 °C
Short-circuit temperature (max.)
+250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeCap [uF/km]DI [mm]RI [Ohm/km]Wi [mm]Ibl [A]Ibe [A]Ik [kA]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x50/16CuRM0.1720.50.3875.52392227.12.1600301166
1x70/16CuRM0.1922.10.2685.5297271102.1640321409
1x95/16CuRM0.2123.60.1935.536132313.62.1660331675
1x120/16CuRM0.2325.10.1535.541636717.12.1700351968
1x150/25CuRM0.2526.50.1245.547040921.42.1720362320
1x185/25CuRM0.2728.10.0995.553846126.42.1760382697
1x240/25CuRM0.330.60.0755.563453234.32.1800403303
1x300/25CuRM0.32330.065.572459942.92.1860433978
1x400/35CuRM0.3635.60.0475.582967157.22.1900454925
1x500/35CuRM0.438.80.0375.595375471.42.1980496006

18/30 kV

Voltage
18/30 kV
Test voltage
63 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
+90 °C
Short-circuit temperature (max.)
+250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeCap [uF/km]DI [mm]RI [Ohm/km]Wi [mm]Ibl [A]Ibe [A]Ik [kA]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x50/16CuRM0.1325.50.38782412257.12.1700351405
1x70/16CuRM0.1527.10.2688299274102.1740371646
1x95/16CuRM0.1628.60.193836332713.62.1760381926
1x120/16CuRM0.1730.10.153841837117.12.1800402227
1x150/25CuRM0.1931.50.124847241421.42.1820412590
1x185/25CuRM0.233.10.099853946626.42.1860432975
1x240/25CuRM0.2235.60.075863553934.32.1900453594
1x300/25CuRM0.24380.06872560642.92.1960484300
1x400/35CuRM0.2640.60.047883168057.22.11020515290
1x500/35CuRM0.2943.80.037895376571.42.41080546403